KVA BASE RATING : 25

FRAME : BC18F

CONTROL SYSTEM

SELF EXCITED ( NO PMG )

AVR

Std : SX460

Optional : SA421

VOLTAGE REGULATION

1.00%

0.50

WITH 4% ENGINE GOVERNING SX460 IS STANDARD AVR

INSULATION SYSTEM

CLASS H

PROTECTION

IP23 STANDARD

RATED POWER FACTOR

0.8 LAG

STATOR WINDING

DOUBLE LAYER CONCENTRIC

WINDING PITCH

TWO THIRD

WINDING LEADS

12

OVERLOAD

10% OVERLOAD FOR 1 HOUR ONCE EVERY 12 HOURS

WAVE FORM DISTORTION

NO LOAD <1.8%, NON DISTORTING BALANCED LINEAR LOAD < 5%

MAXIMUM OVERSPEED

2250 REV / MIN

BEARING DRIVE END

BALL 6309-2RS ( ISO )

BEARING NON-DRIVE END

BALL 6306-2RS ( ISO )

VOLTAGE SERIES STAR (Y)

415 / 240

FREQUENCY HZ

50

WEIGHT COMP. GENERATOR

154

WEIGHT WOUND STATOR

55

WEIGHT WOUND ROTOR

52.5

WR2 INERTIA KGM2

0.1909

% EFFICIENCY @ 0.8 PF AND 100% LOAD

86.9

COOLING AIR

0.095 M3 / SEC

STATOR WINDING RESISTANCE (L-L) @ 22 DEG C

0.5 OHMS

ROTOR WINDING RESISTANCE AT 22 DEG C

0.74 OHMS

Xd DIR AXIS SYNCHRONOUS

1.39

X’d DIR AXIS TRANSIENT

0.15

X"d DIR AXIS SUBTRANSIENT

0.09

Xq QUAD AXIS REACTANCE

0.70

X"q QUAD AXIS SUBTRANSIENT

0.16

XL LINKAGE REACTANCE

0.05

X2 NEGATIVE SEQUENCE

0.13

X0 ZERO SEQUENCE

0.06

REACTANCES ARE SATURATED

VALUES ARE PER UNIT AT RATINGS AND VOLTAGE INDICATED

T’d TRANSIENT TIME CONSTANT

0.022

T"d SUBTRANSIENT TIME CONSTANT

0.0055

T’ do O.C. FIELD TIME CONSTANT

0.45

Ta ARMATURE TIME CONSTANT

0.0065

SHORT CIRCUIT RATIO

0.719

ALL RATINGS ARE INDUSTRIAL , FOR CONTINUOUS DUTY , 3 PHASE ON 40 deg C AMBIENT TEMPERATURE AND 1000 M ALTITUDE

CONTINUOUS DEVELOPMENT OF OUR PRODUCTS ENTITIES US TO CHANGE SPECIFICATION DETAILS WITHOUT NOTICE.